Radio Receiver RF Rx EN868-1
- Product Code: RF Rx EN868-1
- Availability: In Stock
Radio Receiver RF Rx EN868-1
Features/Options
- EnOcean standard
- 1-channel: potential-free relay output
- DC version: 1 change-over contact, NPN or PNP output,
AC version: 1 change-over contact - Transmitter/receiver assignment by teaching mode
- LEDs for indication of switching state
- SMA plug-in connector for external antenna
Product image
Technical Data
Standards | EN 60947-5-1; EN 61000-6-2; EN 61000-6-3; EN 60068-2-6; EN 60068-2-27; EN 301 489-1; EN 301 489-3; EN 300 220-2 |
---|---|
Number of channels | 1 |
Mounting | DIN rail mounting |
Connection | terminals with CAGE CLAMP WAGO Serie 236: 0.08 ... 2.5 mm² AWG 28–14 (incl. conductor ferrules) |
Degree of protection | IP 20 per IEC/EN 60529 |
Inputs | 1 radio channel, max. 10 transmitters per channel |
Outputs | 1 change-over contact (relay) |
Rated operating current Ie |
max. 0.22A AC; 0.08A DC |
Rated operating voltage Ue |
24 V AC/DC -15% ... +10% |
Ie/Ue of output contacts | 6A / 250 VAC; 2A / 24 VDC |
Utilisation category | AC-15; DC-13 |
Ui | 250 VAC |
Uimp | 2.5 kV |
Frequency | 868.3 MHz |
Display | green LED: operating voltage, orange LED: switching conditions |
Switching frequency | approx. 9000 telegrams at repetitions/h |
Degree of pollution | 2 per DIN VDE 0110 |
Ambient temperature | 0°C ... +55°C |
Storage and transport temperature | -25°C ... +85°C |
Vibration resistance | NO 20g, NC 5g |
Shock resistance | max. 100g |
External antenna | always required for optimum sensing range |
Note | inductive loads (contactors, relays etc.) are to be suppressed by suitable circuitry. |
Approvals |
RF Rx EN868-1W, 24 VDC
Optimum Possible UnsuitableArrangement of receiver and switch antenna
mounting mounting mounting
Note
The antenna must be mounted on a metal plate
of min. 250 x 250 mm size.