Code: |
|
|
Name:
|
mV / mA Signal Converter. Low response time. SIL 2
|
|
Type:
|
|
|
Supply:
|
24 V nom (20 to 30 V) reverse polarity protected
|
|
Field device:
|
|
|
Channels:
|
1
|
|
Description:
|
The single channel DIN Rail mV/mA Converters, D1010S-054, D1010S-056, D1010S-057, convert a mV signal from sensors located in Hazardous Area, and repeat the current in floating circuit to drive a Safe Area load.
|
|
Hazardous area:
|
Input: -5 to +35 mV
|
|
Safe area:
|
Output: 4 to 20 mA, on 250 Ohm load in source mode. Response time: 25 ms (10 to 90 % step change) with 8,6 dB of NMRR or 40 ms (10 to 90 % step change) with 21 dB of NMRR; to be specified.
|
|
Function:
|
1 channel I.S. analog input, provides 3 port isolation (input/output/supply) and current (source) output signal.
|
|
SIL level:
|
D1010S-056, according IEC 61508 & IEC 61511, is suitable for applications up to safety integrity level SIL 2 .
Please see our Functional Safety Manual for details.
|
|
Datasheet:
|
|
DTS0197 |
D1010S-056 English datasheet (PDF 195 KB) |
|
|
DTS0292 |
D1010S-056 Italiano datasheet (PDF 215 KB) |
|
|
|
Instruction manual:
|
|
ISM0071 |
Functional Safety manual for SIL 2, SIL 3 applications (PDF 554 KB) |
|
|
ISM0075 |
Installation of Electronic Equipments in Cabinets (PDF 78 KB) |
|
|
ISM0102 |
General D1000 Series Instruction Manual (PDF 2.39 MB) |
|
|
ISM0098 |
D1010-054 -056 -057 (PDF 87 KB) |
|
|
ISM0092 |
Russian language Functional Safety manual for SIL 2, SIL 3 applications (PDF 525 KB) |
|
|
|
Certifications:
|
|
CRT003 |
ATEX DMT 01 ATEX E 042 X (PDF 5.56 MB) |
|
|
CRT013 |
EXIDA SIL2 SIL3 Analysis (03/07-24) (PDF 408 KB) |
|
|
CRT014 |
Metrological Certificate for D1000 Series (Russia) (PDF 307 KB) |
|
|
CRT035 |
TÜV SIL Certificate Summary (PDF 555 KB) |
|
|
CRT040 |
TÜV SIL Report for D1010-054, D1010-056, D1010-057 (PDF 223 KB) |
|
|
CRT047 |
ATEX Certificate D1000 Series by IMQ (PDF 1.02 MB) |
|
|
|
Various:
|
|
|
|