Code: |
|
|
Name:
|
Quad Channel LEDs Isolating Driver.
|
|
Type:
|
|
|
Supply:
|
24 Vdc nom (21.5 to 30 Vdc)
|
|
Field device:
|
|
|
Channels:
|
4
|
|
Description:
|
The D104* series are quad channel DIN Rail Digital Output Modules enabling a Safe Area contact, logic level or drive signal, to control a device in Hazardous Area, providing 3 port isolation (input/output/supply). Typical applications includes driving signalling LED’s, visual or audible alarms to alert a plant operator or driving a solenoid valve or other process control devices. It can also be used as a controllable supply to power measuring or process control equipment in Hazardous Area. Output channels can be paralleled if more power is required; 2 or 3 channels in parallel (depending on the model) are still suitable for Gas Group II C. Four basic models meet a large number of applications: it is possible to obtain 16 different combinations of safety parameters and driving currents.
|
|
Hazardous area:
|
LED or other low power devices.
|
|
Safe area:
|
Dry contact, Logic Level, or Loop Powered 24 Vdc from DCS, PLC or other control devices.
|
|
Function:
|
4 channels I.S. actuated indipendently or in parallel to operate Hazardous Area loads from contacts, logic levels or drive logics in Safe Area providing 3 port isolation (input/output/supply), loop or bus powered.
|
|
Features:
|
• Output to Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2.
• Voltage input, contact, logic level, common positive or common negative, loop powered or bus powered.
• Flexible modular multiple output capability.
• Output short circuit proof and current limited.
• Three port isolation, Input/Output/Supply.
• EMC Compatibility to EN61000-6-2, EN61000-6-4.
• High Reliability, SMD components.
• High Density, four channels per unit.
• Simplified installation using standard DIN Rail and plug-in terminal blocks.
• 250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.
|
|
SIL level:
|
D1041Q, according to IEC 61508, is suitable for applications up to level SIL 3.
|
|
Datasheet:
|
|
DTS0038 |
D1041Q datasheet (English) (PDF 487 KB) |
|
|
DTS0075 |
D1041Q datasheet (Italiano) (PDF 601 KB) |
|
|
DTS0213 |
D1041Q datasheet (Pусский) (PDF 644 KB) |
|
|
|
Instruction manual:
|
|
ISM0020 |
D1041Q instruction manual (PDF 681 KB) |
|
|
ISM0102 |
General D1000 Series Instruction Manual (PDF 2.39 MB) |
|
|
ISM0134 |
UL Control Drawing for D1041Q (PDF 124 KB) |
|
|
|
Certifications:
|
|
CRT003 |
ATEX DMT 01 ATEX E 042 X (PDF 9.52 MB) |
|
|
CRT005 |
UL & C-UL (PDF 81 KB) |
|
|
CRT010 |
Rostehnadzor for D1000 and T3010 Series (Russia) (PDF 730 KB) |
|
|
CRT011 |
Gost R Certificate for D1000 Series (Russia) (PDF 2.00 MB) |
|
|
CRT014 |
Metrological Certificate for D1000 Series (Russia) (PDF 202 KB) |
|
|
CRT017 |
EXIDA SIL2 SIL3 Analysis (04/10-26) (PDF 377 KB) |
|
|
CRT020 |
FM 3024643 (USA) & FM-C 3029921C (Canada) (PDF 3.42 MB) |
|
|
CRT028 |
Korean Register Type Approval Certificate (PDF 577 KB) |
|
|
CRT032 |
IECEx Certificate for D1000 Series (PDF 2.80 MB) |
|
|
CRT047 |
ATEX Certificate D1000 Series by IMQ (PDF 2.09 MB) |
|
|
CRT125 |
IECEx Zone 2 Applications for D1000 Series (PDF 60 KB) |
|
|
CRT144 |
DNV Maritime Type Approval Certificate (D1000 Series) (PDF 223 KB) |
|
|
|
Application notes:
|
|
APN0007 |
Universal AC Power Supply for Series D1000 (PDF 44 KB) |
|
|
APN0010 |
Digital Unit Testing for D1000 Models (PDF 212 KB) |
|
|
|
Accessories:
|
BUS |
Power Bus Optional Enclosure |
|
|
Various:
|
|
|
News:
|
[Certifications and Reports] IECEx Certifications for D1000 Series now available
|
|