Code: |
|
|
Name:
|
2 Ch, mA-V Input, mA-V Output, SW Programmable
|
|
Type:
|
|
|
Supply:
|
12-24 Vdc nom (10 to 30 Vdc)
|
|
Field device:
|
|
|
Channels:
|
2
|
|
Description:
|
The D1052D converts two voltage or current inputs from separately powered sources, located in Hazardous Location, and repeats, with isolation, the signals to drive two independent Safe Area loads. Output Signals can be direct or reverse. All settings are easily programmable via software. Approved for Div. 2 installation.
|
|
Hazardous area:
|
4-20 mA / 0-20 mA or 1-5 V / 0-5 V / 0-10 V from external powered Tx or other instruments.
|
|
Safe area:
|
4-20 mA/0-20 mA or 1-5 V/0-5 V or 2-10 V/0-10 V output signal totally isolated from Input and Supply.
|
|
Function:
|
2 channels I.S. input from separately powered transmitters. Provides 3 port isolation (input/output/supply) and current or voltage output signal.
|
|
Features:
|
• Input from Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2.
• 0/4-20 mA, 0/1-5 V, 0/2-10 V Input-Output Signal linear or reverse.
• High Accuracy, μP controlled A/D converter.
• Three port isolation, Input/Output/Supply.
• EMC Compatibility to EN61000-6-2, EN61000-6-4.
• Fully programmable operating parameters.
• High Reliability, SMD components.
• High Density, two channels per unit.
• Simplified installation using standard DIN Rail and plug-in terminal blocks.
• 250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.
|
|
Datasheet:
|
|
DTS0040 |
D1052D datasheet (English) (PDF 462 KB) |
|
|
DTS0077 |
D1052D datasheet (Italiano) (PDF 463 KB) |
|
|
DTS0214 |
D1052D datasheet (Pусский) (PDF 510 KB) |
|
|
|
Instruction manual:
|
|
ISM0015 |
D1052D instruction manual (PDF 519 KB) |
|
|
ISM0062 |
Manual Configuration Table (PDF 76 KB) |
|
|
ISM0102 |
General D1000 Series Instruction Manual (PDF 2.39 MB) |
|
|
ISM0137 |
UL Control Drawing for D1052S, D1052D, D1052X, D1052Y (PDF 129 KB) |
|
|
|
Certifications:
|
|
CRT003 |
ATEX DMT 01 ATEX E 042 X (PDF 9.52 MB) |
|
|
CRT005 |
UL & C-UL (PDF 81 KB) |
|
|
CRT010 |
Rostehnadzor for D1000 and T3010 Series (Russia) (PDF 730 KB) |
|
|
CRT011 |
Gost R Certificate for D1000 Series (Russia) (PDF 2.00 MB) |
|
|
CRT014 |
Metrological Certificate for D1000 Series (Russia) (PDF 202 KB) |
|
|
CRT020 |
FM 3024643 (USA) & FM-C 3029921C (Canada) (PDF 3.42 MB) |
|
|
CRT028 |
Korean Register Type Approval Certificate (PDF 577 KB) |
|
|
CRT032 |
IECEx Certificate for D1000 Series (PDF 2.80 MB) |
|
|
CRT047 |
ATEX Certificate D1000 Series by IMQ (PDF 2.09 MB) |
|
|
CRT125 |
IECEx Zone 2 Applications for D1000 Series (PDF 60 KB) |
|
|
CRT144 |
DNV Maritime Type Approval Certificate (D1000 Series) (PDF 223 KB) |
|
|
|
Application notes:
|
|
APN0005 |
D1052-53, D1072-73 Signal Converter DIN Rail (PDF 25 KB) |
|
|
APN0007 |
Universal AC Power Supply for Series D1000 (PDF 44 KB) |
|
|
|
Software:
|
SWC1090 |
D1000 and E1000 Software Configurator for Windows |
|
|
|
Accessories:
|
BUS |
Power Bus Optional Enclosure |
PPC1090 |
Pocket Portable Configurator for D105* D106* D107* |
PPC1092 |
D1000 Series Serial Adapter Configurator. |
USBADAPT |
RS-232 to USB Adapter. |
|
|
Various:
|
|
|
News:
|
[Certifications and Reports] IECEx Certifications for D1000 Series now available
[Certifications and Reports] D1000 Series DNV Certificate for Ships and Offshore
|
|